CALL US TODAY: +1 (833) 338-8901

DEUTZ North American Tier 4 Gensets (DOC only)

DEUTZ manufactures and tests complete power generator sets, ensuring quality, performance and the continuous power that customers have come to expect, off the power grid. The Standard DPS package includes various features and can be customized to meet a wide range of application requirements.

For a continuous power supply that functions regardless of power grid disruptions, try our electrical generator. We're known for our backup power solutions that function as a reliable electrical source regardless of power outages. Enjoy a reliable power supply of electrical energy at all times, even during periods of grid failure, by using a DEUTZ electrical generator.

Contact Us
General Details
Standard PackageGenset Completion Kit Options
DEUTZ generating set, single-source responsibility.Loose control panels – auto start and auto mains failure
Standard DEUTZ warranty and service package.Loose controller – Deep Sea 4520 module
DEUTZ factory-built and tested.Wiring harness and extension harness for above (approximately six ft)
Unit-mounted radiator with 50°C (122°F) ambient.Exhaust flex pipe
Complete with fan guards, mounted air cleaner and exhaust aftertreatment.Remote and top DOC kit including heat-wrap options
Close-coupled, brushless, rotating-field alternator with broad range of reconnection options.Anti-shock mounts (quantity of 4, supplied loose)
Cross rails for base-frame mounting or customer machine installation.Generator set lifting provision
Extra fuel-transfer pump for high-lift applications
PCV heater
Block heater
Acceptance test report – 22000473

Rating Definition

Prime Rating (PRP)

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation on the annual hours of operation, and this model can supply 10% overload power for one hour in a 12 hour period.

Standby Rating (LTP)

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

Standard Reference Conditions

Standard reference conditions include a 25°C (77°F) air inlet temp, 100m (328 ft) A.S.L. 30% relative humidity.

Technical Details
WATER-COOLED ENGINES
GENSET MODELSDPS 27DPS 50DPS 60
Rated Speed (rpm)180018001800
Rated voltage, 3 phase (V)240/480240/480240/480
Rated power 0.8 power factor (PRP) 3 phase (KVA)254550
Rated power 0.8 power factor (LTP) 3 phase (KVA)275056
Rated power (PRP) 3 phase (kWe)193640
Rated power (LTP) 3 phase (kWe)224045
Nominal current (LTP) 480 V 3 phase (A)326072
Generator output reconnectable ratings (V)For details please refer to DEUTZ Application department or local DEUTZ DealerFor details please refer to DEUTZ Application department or local DEUTZ DealerFor details please refer to DEUTZ Application department or local DEUTZ Dealer
Engine
ModelD2.9TD2.9TD 3.6
Rated PRP gross power (kW)23.341.546.9
Rated LTP gross power (kW)25.946.152.1
Rated PRP gross power (HP)31.255.662.8
Rated LTP gross power (HP)34.761.769.8
Speed governorElect G2Elect G2Elect G2
Number of cylinders444
Engine configurationILILIL
Exhaust after treatmentDOCDOCDOC
Displacement (ltr)2.902.903.6
Bore/stroke (mm)92/11092/11098/120
Electrics (V/dc)121212
Fuel specificationASTM D975ASTM D975ASTM D975
Generator
MakeDEUTZDEUTZDEUTZ
ModelECP28-2L/4ECP32-1M/4ECP32-2M/4
Generator efficiency (%)89.990.591.3
Estimated Fuel Consumption
Specific Fuel Consump (g/kW/h)236231217
Fuel @ 75% duty cycle (l/h)5.469.5110.09
Fuel @ 75% duty cycle (USgal/h)1.442.512.66
Emission Certification
EPA/CARBTier 4 fTier 4 fTier 4 f
Weights and Dimension
Genset w/o panel (dry) (kg)527608823
Length (mm)154117541805
Width (mm) 676655734
Height (mm)117310821102